CVE-2025-9041
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
Scoring
- Severity
- HIGH
- CVSS base score
- 8.7
- CVSS vector
- CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
- EPSS probability
- 0.32%
- CWE
- CWE-1287
- Published
- 2025-08-14
- Last modified
- 2026-03-12
Affected products
- Rockwell Automation FLEX 5000 I/O
Weakness type