# CVE-2025-2523

## Summary

- **CVE ID:** CVE-2025-2523
- **Severity:** CRITICAL
- **CVSS Score:** 9.4 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H)
- **CWE:** CWE-191
- **Published:** Jul 10, 2025
- **Last Modified:** Mar 12, 2026

## Description

The Honeywell Experion PKS 

 and OneWireless WDM 

contains an Integer Underflow 

vulnerability 

in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to a Communication Channel Manipulation, which could result in a failure during subtraction allowing remote code execution.



Honeywell recommends updating to the most recent version of 

Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1.



The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E.  The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.

## Affected Products

- Honeywell — C300 PCNT02 (520.1)
- Honeywell — C300 PCNT02 (530)
- Honeywell — C300 PCNT05 (520.1)
- Honeywell — C300 PCNT05 (530)
- Honeywell — FIM4 (520.1)
- Honeywell — FIM4 (530)
- Honeywell — FIM8 (520.1)
- Honeywell — FIM8 (530)
- Honeywell — UOC (520.1)
- Honeywell — UOC (530)
- Honeywell — CN100 (520.1)
- Honeywell — CN100 (530)
- Honeywell — HCA (520.1)
- Honeywell — HCA (530)
- Honeywell — C300PM (520.1)
- Honeywell — C300PM (530)
- Honeywell — C200E (520.1)
- Honeywell — C200E (530)
- Honeywell — Wireless Device Manager (322.1)
- Honeywell — Wireless Device Manager (330.1)

## References

- [CNA](https://process.honeywell.com/)

## Exploitation Prediction (EPSS)

- **EPSS Score:** 0.72%
- **EPSS Percentile:** 51.7

---
_Exported from OnDuty AI Vulnerability Intelligence on 2026-09-10._