CVE-2024-22387

External Control of Critical State Data (CWE-642) in the Controller 6000 and Controller 7000 diagnostic web interface allows an authenticated user to modify device I/O connections leading to unexpected behavior that in some circumstances could compromise site physical security controls. Gallagher recommend the diagnostic web page is not enabled (default is off) unless advised by Gallagher Technical support. This interface is intended only for diagnostic purposes. This issue affects: Gallagher Controller 6000 and 7000 9.10 prior to vCR9.10.240520a (distributed in 9.10.1268(MR1)), 9.00 prior to vCR9.00.240521a (distributed in 9.00.1990(MR3)), 8.90 prior to vCR8.90.240520a (distributed in 8.90.1947 (MR4)), 8.80 prior to vCR8.80.240520a (distributed in 8.80.1726 (MR5)), 8.70 prior to vCR8.70.240520a (distributed in 8.70.2824 (MR7)), all versions of 8.60 and prior.

Scoring

Severity
MEDIUM
CVSS base score
6.8
CVSS vector
CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:N/I:H/A:H
EPSS probability
0.31%
CWE
CWE-642
Published
2024-07-11
Last modified
2026-03-13

Affected products

Weakness type

Related vulnerabilities

Markdown version · Browse all CVEs